TGH33 (150KVA~250KVA)
PV-ESS All-in-One Series
Product advantages
Intelligent management
Supports multiple working modes: load priority, battery priority, peak shaving and valley filling, with flexible configurations based on different scenarios
High battery compatibility
Supports battery management capabilities and is compatible with multiple BMS protocols
DC coupling
Photovoltaic and battery direct connection to DC busbars offers high efficiency and low cost
Highly adaptable
HPS's wide grid input range can solve electricity needs in unstable areas; It also offers high load impact resistance.
Technical specifications
Model TGH150 TGH250
Rated Capacity [kVA] 165 275
Rated Power [kW] 150 250
Rated Voltage 400Vac
AC System Three-phase five-wire(3W+N+PE)
Voltage Range 320~460Vac
Rated Output Voltage 400Vac±1%
Rated Frequency 50Hz/60Hz
Frequency Range 45~55Hz/55~65Hz
Isolation Transformer Standard Configuration
Battery Pack Voltage 486~864Vdc
Number of Battery Cells 180~240 Cells (Lithium Battery)
Working Mode Load Priority, Battery Priority, Peak Shaving and Valley Filling
PV PV Open-Circuit Voltage 900Vdc
MPPT Voltage Range 200~850Vdc
PV Maximum Power 3*60kW
MPPT Rated Power 60kW
MPPT Startup Voltage 250Vdc
PV Maximum Current 3*120A
Number of MPPTs 3
Rectification Input Voltage Range 320~460Vac
Rated Frequency 50Hz/60Hz(Background Setting)
Frequency Range 50Hz/60Hz ±5Hz
Inversion Inverter Output Voltage Three-phase five-wire(3W+N+PE) 400Vac
Output Phase Voltage Setting 220Vac/230Vac/240Vac(Background Setting)
Output Voltage Accuracy ±1%
Voltage Transient Range ±5%
Transient Recovery Time 20ms
Rated Frequency 50Hz/60Hz±1%(Background Setting)
Frequency Tracking Range 50Hz/60Hz±3 Hz
Crest Factor 0.125694444
Waveform Sine Wave
Waveform Distortion ≤3% (Linear Load)
Voltage Unbalance ±3% (100% Unbalanced Load)
Overload When load rate >105% and ≤110%: Switch to bypass after 1 hour, automatic recovery after load reduction.
When load rate >110% and ≤125%: Switch to bypass after 10 minutes, automatic recovery after load reduction.
When load rate >125% and ≤150%: Switch to bypass after 1 minute, automatic recovery after load reduction.
When load rate >150% and ≤200%: System shuts down directly after 10 seconds, restart after user confirms load reduction.
When load rate >200%: System shuts down immediately, restart after user confirms load reduction
Short Circuit System current limiting, shuts down immediately, restart after user confirmation.
Bypass Rated Voltage Three-phase five-wire(3W+N+PE) 400Vac
Voltage Range ±20%
Rated Frequency 50/60Hz±5Hz
Battery Battery Capacity Configurable
Cut-off Discharge Voltage (25℃) Configurable
Charging Current Setting Lithium Battery: 0.5C (factory setting), 0.05~2.0C (Configurable);
Depth of Discharge Setting Configurable
Conversion Time Inverter to Bypass Switching 0 ms
Bypass to Inverter Switching 0 ms
Communication Interface Remote Control Input Inverter ON/OFF, Abnormality Clear, Emergency Shutdown
Computer Monitoring Port RS232, RS485, LAN, SNMP (Optional), Wi-Fi (Optional), 4G (Optional)
Dry Contact Output12Vdc/250Vac 1A Max Bypass Input Abnormality, Rectifier Input Abnormality, System Fault, System Alarm, Low Battery Voltage, Output Overload, Fan Fault, Generator ON/OFF (Configurable)
Environment Operating Temperature 0~40℃
Maximum Relative Humidity 90% (Non-condensing)
Maximum Altitude Rated power at 2000 m (1% power reduction per 100 m elevation increase), max. 4000 m
Others Dimensions 1400(W)*800(D)*1800(H)mm
Unit Weight /
Cooling Forced Ventilation
Noise (1m from the unit, value varies with load and temperature) 65 dB
Mean Time Between Failures (MTBF) 200,000 h
Protection Class (EN60529) IP20
Incoming Line Mode Bottom Incoming Line
Mounting Mode Cabinet-type Fixed Mounting
To learn more about energy storage solutions, please contact us!